Strany 1 - Maintenance Manual

LogiCool™ OnRak IT Cooling Technical, Installation, Operational and Maintenance Manual

Strany 2

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 10 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Strany 3

IT Cooling LogiCool™ OnRak IT Cooling 11 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Dual Power Supply Dual supply

Strany 4 - Health and Safety

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 12 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Te

Strany 5

IT Cooling LogiCool™ OnRak IT Cooling 13 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Cooling Performance LOR 6042U-C0

Strany 6

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 14 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Co

Strany 7

IT Cooling LogiCool™ OnRak IT Cooling 15 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Cooling Performance LOR 8042U-C0

Strany 8

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 16 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Co

Strany 9

IT Cooling LogiCool™ OnRak IT Cooling 17 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Ethylene Glycol Correction Facto

Strany 10

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 18 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 M

Strany 11

IT Cooling LogiCool™ OnRak IT Cooling 19 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Dimensional Data Dimensions

Strany 12 - Technical Data

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 2 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Abo

Strany 13

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 20 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 S

Strany 14

IT Cooling LogiCool™ OnRak IT Cooling 21 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Pipework Schematics Scheme 1 

Strany 15

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 22 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Pi

Strany 16

IT Cooling LogiCool™ OnRak IT Cooling 23 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Installation IMPORTANT If the

Strany 17

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 24 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 F

Strany 18 - Pressure drop kPa

IT Cooling LogiCool™ OnRak IT Cooling 25 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Rack Support Wheel A support whe

Strany 19

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 26 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 D

Strany 20 - Noise Data

IT Cooling LogiCool™ OnRak IT Cooling 27 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Floor Cut Outs To enable the fl

Strany 21

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 28 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 W

Strany 22 - Pipework Schematics

IT Cooling LogiCool™ OnRak IT Cooling 29 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Flexible Water Connection Pipew

Strany 23

IT Cooling LogiCool™ OnRak IT Cooling 3 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Warranty Warranty All AIAC produc

Strany 24 - Fitting Hinges

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 30 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 C

Strany 25

IT Cooling LogiCool™ OnRak IT Cooling 31 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Chilled Water Valve (3 Wa

Strany 26 - CAUTION

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 32 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 C

Strany 27

IT Cooling LogiCool™ OnRak IT Cooling 33 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Solenoid Valve The solenoid

Strany 28 - Water Connections

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 34 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 C

Strany 29

IT Cooling LogiCool™ OnRak IT Cooling 35 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013  Attach the earth strap to t

Strany 30

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 36 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Un

Strany 31

IT Cooling LogiCool™ OnRak IT Cooling 37 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Uninterrupted Power Supply The

Strany 32

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 38 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Ra

Strany 33

IT Cooling LogiCool™ OnRak IT Cooling 39 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Rack Sealing The rack must be

Strany 34

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 4 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Hea

Strany 35

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 40 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 In

Strany 36

IT Cooling LogiCool™ OnRak IT Cooling 41 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Automatic Fan Disconnect Th

Strany 37

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 42 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 C

Strany 38 - Management

IT Cooling LogiCool™ OnRak IT Cooling 43 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 1. ALARM Whe

Strany 39

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 44 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Ex

Strany 40 - Interconnecting Wiring

IT Cooling LogiCool™ OnRak IT Cooling 45 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Enabling the Unit

Strany 41

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 46 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 D

Strany 42 - Controls

IT Cooling LogiCool™ OnRak IT Cooling 47 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Temperature Sensor Locations

Strany 43

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 48 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Mo

Strany 44 - Navigation

IT Cooling LogiCool™ OnRak IT Cooling 49 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Load Neutral Mode When operat

Strany 45

IT Cooling LogiCool™ OnRak IT Cooling 5 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 CONTENTS About Airedale Products

Strany 46 - Modulated Cooling

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 50 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Ra

Strany 47

IT Cooling LogiCool™ OnRak IT Cooling 51 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Commissioning Procedure Genera

Strany 48 - Modes of Operation

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 52 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Co

Strany 49

IT Cooling LogiCool™ OnRak IT Cooling 53 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Maintenance Changing EC Fans

Strany 50 - Rack Pressure Management

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 54 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Op

Strany 51

IT Cooling LogiCool™ OnRak IT Cooling 55 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Troubleshooting FAULT POSSIBLE

Strany 52 - Commissioning Procedure

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 56 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Strany 53

IT Cooling LogiCool™ OnRak IT Cooling 57 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013

Strany 54

Head Office: Airedale International Air Conditioning Ltd Leeds Road Rawdon Leeds LS19 6JY United Kingdom Tel: +44 (0) 113 239 1000 Fax:

Strany 55

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 6 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Spe

Strany 56

IT Cooling LogiCool™ OnRak IT Cooling 7 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Standard Features The OnRak unit

Strany 57

LogiCool™ OnRak Active Cabinet Exhaust IT Cooling 8 IT Cooling Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Rac

Strany 58 - Head Office:

IT Cooling LogiCool™ OnRak IT Cooling 9 Technical, Installation and Maintenance Manual :6912497 V1.5.0 02_2013 Optional Features The OnRak uni